How to Send a COV Broadcast to an ECB Device

How to Send a COV Broadcast to an ECB Device

 

1- Double-click on Network Value block:

  • Set Network value mode to Output
  • Set Configuration type to Database
  • Set Service to Send Local Broadcast COV
  • Set Device path to the “hub device’s” path
  • Set Object to the one located on the “hub device”

2- Double-click on Analog\Binary\Multi State Value block :

  • Set COV min send time/max send time/increment accordingly
  • Set Default value accordingly

3- Launch GFX from the “target device”:

  • Open the Distech Controls Toolbox
  • Open Inputs and Outputs Ø Drag a Network Value to the Programming sheet

4- Double-click on Network Value block:

  • Set Network value mode to Intput
  • Set Configuration type to Database
  • Set Service to Receive Broadcast COV
  • Set Device path to the “hub device’s” path (it should only accept messages from the desired hub device)
  • Set Object to the one located on the “hub device”
  • Set Max receive time accordingl
  • Set Default value accordingly

Launch GFX from hub device:
  • Open the Distech Controls Toolbox
  • Open Inputs and Outputs Ø Drag a Network Value to the Programming sheet
  • Open Constants & Variables Ø Drag an Analog\Binary\Multi State Value Programming sheet

Add Feedback