Distech Controls - EC-RTU-L Using ACI TUC Sensor

Using an ACI TUC sensor with an EC-RTUL controller:
 

Input Configuration:
Select Setpoint Input
Change SNVT type to SNVT_temp_P
Input Signal Interpretation: Setpoint Offset
Signal Type: Voltage 0-10
Offset = 0
Max Value = 7.2
Min Value = -8

Occupied/Bypass Heat Setpoint = 72.5
Occupied/Bypass Cool Setpoint = 73.5

Be sure the controller is in the Occupied mode
Check the NVO_EffectiveSetpoint Value

Add Feedback